Ucontrol Pty Ltd Australia

2000-35-013 CT

50A CURRENT TRANSFORMER WITH 4-20MA  

Current transformer code 2000.35.013 ia an AC / DC TRMS transformer galvanically isolated  form the measuring circuit.  The device is similar to a standard active current transformer, both in terms of operation and appearance, but is can measure both AC & DC current.

The transformer is powered by 4-20mA output loop, the measuring principle is hall effect  and this provides a remarkable 0.5% accuracy

TECHNICAL DATA

Power supply 11-35VDC 

Loop powered 4-20mA 2 wire 
 
Galvanic isolation 3 KV

A/D Resolution 12 bits 0.5% full scale

Removable terminals

DIN rail mount (vertical/horizontal)

Temperature -40..+85°C 10..90% RH

IP20 Protection degree

Response speed 1000 ms
 
Overload 2KA Impulsive 300 Continuous
 
Dimmensions 46 x 63 x 26mm
 
Weight 72g
 
Approvals CE, EN 61000-6-4, EN 64000-6-2
EN 61010-1


 

                 Z170REG 4-20mA signal splitter or signal doubler

             signal splitter 4-20 mA or signal duplicator for thermocouple 4-20mA 0-10V signals

INPUT

Current : 25A / 50A TRMS selectable 
by dipswitch, bipolar +/-50 or +/-25 A DC

OUTPUT

4-20mA 12 bit

ORDER CODE 
2000-35-013 Current Transformer with 4-20mA

 

Ucontrol Pty Ltd

S401/15 Albert Ave

Broadbeach QLD 4218

Web: www.ucontrol.com.au  

Tel: 1300 459949